Motor Protective Relay
K2CM
CSM_K2CM_DS_E_6_2
Solid-state Relay Enables Choice of Three
Operating Functions (Overcurrent, Open-
phase, and Reverse-phase)
• Protects 3-phase induction motors and their loads from damage.
• Selection and combination of operating functions from overcur-
rent, open-phase, and reverse-phase.
• Circuit and output relay operation can be checked by just operat-
ing the test button.
• The set time value can be checked easily because operation time
is indicated from the start of operation.
• Space-saving, integrated construction.
Note: If the K2CM is used with an inverter, the operating conditions will
depend on the load wiring length, inverter carrier frequency, basic
frequency, and load conditions. Error will occur in the operating
values of the overload elements. It is recommended to test operation
before using the K2CM.
Model Number Structure
■ Model Number Legend
K2CM-@@@-@@
12 3 4 5 6
1. Model 5. Current setting range
LS: 2 to 8 A
K2CM: Motor relay
2. Mounting style L: 8 to 26 A
None: Surface-mounting, integrated type M: 20 to 65 A
3. Operating time characteristics H: 50 to 160 A
None: Inverse type 6. Operating time
Q: Instantaneous type None: ×1 (2 to 10 s)/ ×4 (8 to 40 s) Switchable
4. Supply voltage of control circuit
7. Resetting method
1: 100/110/120 VAC
None: Manual reset
2: 200/220/240 VAC
A: Automatic reset
4: 400/440 VAC
8. Reverse-phase detection type
None: Current reverse-phase detection
V: Voltage reverse-phase detection
Ordering Information
■ List of Models
Voltage Reverse-phase Detection Models
Time specification Inverse type Instantaneous type
Resetting Current setting range 8 to 26 A 20 to 65 A 50 to 160 A 8 to 26 A 20 to 65 A 50 to 160 A
method
Operating voltage
Manual 200/220/240 VAC K2CM-2LV K2CM-2MV K2CM-2HV K2CM-Q2LV K2CM-Q2MV K2CM-Q2HV
Automatic 200/220/240 VAC K2CM-2LAV K2CM-2MAV K2CM-2HAV K2CM-Q2LAV K2CM-Q2MAV K2CM-Q2HAV
1
K2CM
Current Reverse-phase Detection Models
Time specification Inverse type Instantaneous type
Current setting range
2 to 8 A 8 to 26 A 20 to 65 A 50 to 160 A 2 to 8 A 8 to 26 A 20 to 65 A 50 to 160 A
Resetting
method Operating voltage
Manual 100/110/120 VAC K2CM-1LS K2CM-1L K2CM-1M K2CM-1H K2CM-Q1LS K2CM-Q1L K2CM-Q1M K2CM-Q1H
200/220/240 VAC K2CM-2LS K2CM-2L K2CM-2M K2CM-2H K2CM-Q2LS K2CM-Q2L K2CM-Q2M K2CM-Q2H
400/440 VAC --- K2CM-4L K2CM-4M K2CM-4H --- K2CM-Q4L K2CM-Q4M K2CM-Q4H
Automatic 100/110/120 VAC K2CM-1LSA K2CM-1LA K2CM-1MA K2CM-1HA K2CM-Q1LSA K2CM-Q1LA K2CM-Q1MA K2CM-Q1HA
(See
200/220/240 VAC K2CM-2LSA K2CM-2LA K2CM-2MA K2CM-2HA K2CM-Q2LSA K2CM-Q2LA K2CM-Q2MA K2CM-Q2HA
note.)
400/440 VAC --- K2CM-4LA K2CM-4MA K2CM-4HA --- K2CM-Q4LA K2CM-Q4MA K2CM-Q4HA
Note: The manual resetting method must be used with reverse-phase detection.
■ Related Product
Transformer
Model Voltage specification Secondary power
consumption
SE-PT400 Primary side 380 to 480 V (wide power supply range) 7VA
Secondary side 190 to 240 V (wide power supply range)
Note: Use this Transformer when a voltage reverse-phase detection model is used on a 400-V line.
Specifications
■ Ratings
Other features, such as 100% overcurrent capacity and flush mounting are also available. See Model Number Legend on page 1 for details.
Supply voltage of motor circuit 200/220, 400/440 VAC, 50/60 Hz
Supply voltage of control circuit 100/110/120, 200/220/240, 400/440 VAC, 50/60 Hz
Insulation breakdown of output contact 500 VAC
Operating voltage/current of output contact NO contact: 120 VAC/2 A, 240 VAC/1 A, 440 VAC/0.5 A, 110 VDC/0.2 A, 220 VDC/0.1 A
(pf = 0.4 when breaking contact)
NC contact: 120 VAC/5 A, 240 VAC/2 A, 440 VAC/1 A, 110 VDC/0.2 A, 220 VDC/0.1 A
Contact form of output contact Current reverse-phase detection models: SPST-NO + SPST-NC
Voltage reverse-phase detection models: SPDT
Operating current range of input circuit 2 to 160 A (Number of passes: 1)
Operating voltage range of control circuit 85% to 110% of rated voltage, but operates normally at 50% of open-phase supply voltage
Operating frequency range of control circuit 95% to 105% of rated frequency
Power consumption Approx. 3 VA (in standby state); 5 VA (in operating state)
Overcurrent function operating value 115 ±10% of the setting value
Overcurrent function operating time setting Inverse Type
range
Inverse time both at startup and during operation:
Timer scale × 1 (s) at 600% overload
Timer scale × 3 (s) at 200% overload
Note: The above values are for a time factor setting of 1.
Instantaneous Type
Fixed time at starting (start-up lock)
• Time setting value (varies between 2 and 40 s) at 140% overload and starting
Instantaneous during operation: 0.5 s max. (when current is increased from 100 to 140% of the
set current value)
Case color Munsell 5Y7/1
Overcurrent function operating time Inverse type: ±10% of maximum setting value (at 600% overload)
characteristics Instantaneous type: ±20% of maximum setting value (at 140% overcurrent and at starting)
Overcurrent function resetting value 100% min. of the setting value
Overcurrent function start-up operating Inverse type: Not applicable
value Instantaneous type: 30% max. of the setting value (See note.)
Open-phase operating value 85% max. of the set current value (at open-phase)
Open-phase operating time 2 s max. (at overcurrent operating value)
Reverse-phase operating value 50% max. of the current value (80% max. of the operating voltage)
Reverse-phase operating time 1 s max. (at overcurrent operating value)
Imbalance operating value 85% of the set current value
Current imbalance factor High: 35 ±10%; Low: 60% min. (at overcurrent operating value)
where
Reverse phase portion
Imbalance factor = × 100 (%)
Normal phase portion
Note: The start-up lock timer restarts when the operating value at starting becomes less than 30% of the set current value.
2
K2CM
■ Characteristics
Variation due to At 20 ±20 °C Overcurrent: ±5% of operating value, ±10% of operating time
temperature Open-phase: ±10% of operating value, ±10% of operating time
fluctuation Reverse-phase: ±10% of operating value, ±10% of operating time
At 20 ±30 °C Overcurrent: ±10% of operating value, ±20% of operating time
Open-phase: ±20% of operating value, ±20% of operating time
Reverse-phase: ±20% of operating value, ±20% of operating time
Variation due to At 85% to 110% of Overcurrent: ±5% of operating value, ±10% of operating time
voltage fluctuation rated voltage Open-phase: ±5% of operating value, ±10% of operating time
Reverse-phase: ±5% of operating value, ±10% of operating time
Variation due to At 95% to 105% of
frequency rated frequency
fluctuation
Insulation resistance 10 MΩ min. (between current-carrying terminals and mounting panel)
5 MΩ min. (between current-carrying terminals and between contact poles)
Dielectric strength 2,500 VAC (between current-carrying terminals and mounting panel and between current-carrying
terminals)
1,000 VAC (between contact poles)
Permissible impulse voltage Current reverse-phase detection models:
6,000 V (between current-carrying terminals and mounting panel)
4,500 V (between current-carrying terminals and between control power supply terminals)
Waveform: 1.2/50 μs
Voltage reverse-phase detection models:
4,500 V (between current-carrying terminals and mounting panel)
Waveform: 1.2/50 μs
Overcurrent strength of main circuit No abnormality develops when 20 times the set current value is applied for 2 s, 2 times with a 1-
minute interval.
Overvoltage strength of control power No abnormality develops when 1.15 times the relay’s rated voltage is applied once for 3 hours.
supply circuit
Variation due to waveform distortion No malfunction occurs when pulse containing 100% of the 2nd to 9th harmonics is applied (open-
phase switch set to “Low”). (See note.)
Vibration Malfunction: 10 to 55 Hz, 0.3-mm double amplitude (in X, Y, and Z directions for 10 minutes each)
Destruction: 10 to 25 Hz, 2-mm double amplitude (in X, Y, and Z directions for 2 hours each)
2
Shock
Malfunction: 98 m/s (approx. 10 G) in X, Y, and Z directions
2
Destruction: 294 m/s (approx. 30 G) in X, Y, and Z directions
Test current Operating time Set time value
(reference only)
Setting Approx. ±30% of the maximum setting value
characteristics of
operating time
Service life Electrical: 10,000 operations
Ambient temperature Operating: −10 to 60 °C (with no icing)
Storage: −25 to 65 °C
Humidity 35% to 85%
Altitude 2,000 m max.
Note: This means that no malfunction occurs with the open-phase element, but the operating value of the overload element may vary.
3
K2CM
Connections
■ Voltage Reverse-phase Detection Models
Terminal Arrangement Manual Operation Low-voltage Circuit (High-
capacity Motor)
200 VAC
50/60Hz
RS T
Ta Tc Tb U VW
Stop
Start
Output contacts Control power
(SPDT) supply
Magnet Perform the external connections by referring to the examples given below.
contactor
Obtain the control power supply from the same phase as the power supply to
the magnet contactor coil.
Connect the phase advancing capacitors closer to the power supply than the
current transformer, as shown in the examples.
Phase advancing
capacitorTighten the terminal screws to a torque of 0.98 N·m max. (The appropriate
Current converter for
tightening torque is 0.49 to 0.67 N·m.) Alarm
measuring device @/5A
BZ
buzzer
Use of insulated solderless terminals is recommended for connection to the
Relay terminals (M3.5).
R S T
U V W
Ta Tc Tb U VW
Note: 1. In principle, the K2CM must be surface mounted with the terminal
M
A B C
1 2 3
block facing downward.
Motor
Motor protective relay
2. Use M5 screws with spring washers and flat washers for mounting.
Tighten the screws to a torque of 1.77 N·m max. (The appropriate
tightening torque is 1.08 to 1.57 N·m.)
Automatic Operation Low-voltage Circuit
200 VAC
Manual Operation Low-voltage Circuit
50/60Hz
RS T
200 VAC
50/60Hz
RS T
Stop
Automatic
Start
Magnet contact
contactor
Magnet
contactor
BZ
Phase advancing
Alarm
capacitor
buzzer
BZ
Phase
Alarm
advancing R S T
buzzer
capacitor U V W
Ta Tc Tb U VW
A B C
1 2 3
R S T
U V W
Ta Tc Tb U VW
A B C Motor protective relay
1 2 3
Motor protective relay
M
Motor
M
Motor
Manual Operation High-voltage Circuit
Manual Operating Low-voltage Circuit ( 3, 300 VAC
50/60Hz
RS T
Transformer @/200V
Start)
200 VAC
50/60Hz
RS T
High-tension
X/a
Stop
fuse
Stop
Start
High-voltage
magnet contactor
Start
Auxiliary
X
Magnet relay
contactor
Phase advancing
capacitor
Current converter for
measuring device @/5A
BZ
Alarm
BZ
Alarm
buzzer
Phase buzzer
advancing
R S T
capacitor R S T
U V W U V W
Ta Tc Tb U VW
Ta Tc Tb U VW
M
A B C A B C
1 2 3
1 2 3
High-voltage
motor
Motor protective relay Motor protective relay
changeover
Note: Connect the phase advancing capacitor on the power supply
side of the Motor Protective Relay as shown in the above dia-
M
grams.
4
K2CM
■ Current Reverse-phase Detection Models
Terminal Arrangement Manual Operation Low-voltage Circuit (High-
capacity Motor)
200 VAC
50/60Hz
RS T
a1 c1 b2 C2 S1 S2
Stop
Start
Output contacts Control power
(NO and NC) supply
Magnet Perform the external connections by referring to the examples given below.
contactor
Connect the phase advancing capacitors closer to the power supply than the
current transformer as shown in the examples.
Tighten the terminal screws to a torque of 0.98 N·m max. (The appropriate
tightening torque is 0.49 to 0.67 N·m.)
Phase advancing
capacitor
Use of insulated solderless terminals is recommended for connection to the
Current converter for
Alarm
Relay terminals (M3.5). measuring device @/5A
BZ
buzzer
Note: 1. In principle, the K2CM must be surface mounted with the terminal
block facing downward. R S T
U V W a1 c1 c2
b2 s1 s2
M
2. Use M5 screws with spring washers and flat washers for mounting. A B C
1 2 3
Tighten the screws to a torque of 1.77 N·m max. (The appropriate Motor
Motor protective relay
tightening torque is 1.08 to 1.57 N·m.)
Manual Operation Low-voltage Circuit
Automatic Operation Low-voltage Circuit
200 VAC
200 VAC
50/60Hz
50/60Hz
RS T
RS T
Stop
Start
Automatic
Magnet contact
Magnet
contactor
contactor
BZ BZ
Phase Phase advancing
Alarm Alarm
advancing
capacitor
buzzer
buzzer
capacitor
R S T R S T
U V W
U V W
a1 c1 b2 c2 s1 s2
a1 c1 b2 c2 s1 s2
A B C
A B C
1 2 3
1 2 3
Motor protective relay
Motor protective relay
M
M
Motor
Motor
Manual Operating Low-voltage Circuit (
Manual Operation High-voltage Circuit
Start)
3,300 VAC
50/60Hz
200 VAC RS T
Transformer @/100V
50/60Hz
RS T
High-tension
X/a
Stop Stop
fuse
Start
Start
High-voltage
magnet contactor
Magnet
contactor
Auxiliary
X
relay
Alarm
BZ
Phase advancing
buzzer
Phase
capacitor
advancing
Current converter for
capacitor R S T
U V W
measuring device @/5A
a1 c1 b2 c2 s1 s2
A B C BZ
1 2 3
Alarm
buzzer
Motor protective relay
changeover
R S T
U V W a1 c1 c2 s1 s2
b2
M
A B C
1 2 3
M High-voltage
motor
Motor protective relay
Note: Connect the phase advancing capacitor on the power supply
side of the Motor Protective Relay as shown in the above
diagrams.
5
K2CM
Output Circuits
■ Internal Circuit and Operation Description
Voltage Reverse-phase
Inverse and Instantaneous
Detection Models
Reset button
Types
With the voltage reverse-phase
RS T A
B
S1
detection models, the circuit
Test button
A
As shown on the right, the K2CM section enclosed by in the
C2
diagram on the left is configured as
To each
detects abnormalities in motor M X/b2
circuit
shown below. The circuit section
b2
C
by checking its line current. The enclosed by is not used.
S2
Voltage
C1
motor’s current signal is detected
circuit
1
for test
U
by the current transformer and is a1
X/a1
processed separately for each
V To OR circuit
phase and input to the respec-
W
tive circuits. In each circuit, par-
allel judgement of failure such as
2
overcurrent, open-phase, or
reverse-phase (see note) is
To each circuit
made based on the input signals.
If a failure is detected in a circuit,
Overcurrent
the circuit’s output is input to the indicator Instantaneous Type
LED
indication circuit to illuminate the Open-phase With instantaneous-type
indicator
models, the circuit section
LED
corresponding LED indicator and
Reverse- B
enclosed by is
phase
also input to the relay drive cir- LED configured as shown below.
indicator
cuit to drive relay X, resulting in a
trip signal to be externally output
from it. The three major circuits
To each circuit
are described below.
C
Note: Applies to current reverse-
M
X
phase detection models
only.
3
1) Overcurrent Circuit
Overcurrent Detecting Circuit Starting Time Setting Circuit (Instantaneous Type)
This circuit detects when the current reaches the overcurrent operat- This circuit performs time setting using the VR for setting the start-up
ing level (115% of the set current value). lock time and obtains fixed time-limit characteristics using an RC
time-limiting circuit.
Time Setting Circuit (Inverse Type)
Operation at start-up is shown in the figure below. After the motor
This circuit performs time setting using the VR (variable resistor) for turns ON at point A, the motor’s starting current exceeds the start-up
the operating time setting and obtains inverse-type characteristics operating value and so the RC time-limiting circuit starts charging. If,
using an RC time-limiting circuit. The operating time can be set within for example, the motor current descends below the start-up operat-
a range from 2 to 10 s or 8 to 40 s by operating the setting switch ing value (30% max. of the set current value) at point B before the
using a VR. The VR covers a time range 5 times the standard range. start-up lock time, tc, has elapsed, the RC time-limiting circuit is reset
immediately and when the motor current rises above the start-up
Start-up Detecting Circuit (Instantaneous Type)
operating value again at point C, the RC time-limiting circuit starts
charging again. After the start-up lock time has elapsed (at point D),
Instantaneous-type models output a trip signal instantaneously when
instantaneous operation is enabled. At the start of operation, the
the motor current exceeds the overcurrent operating value (115% of
motor current is at its peak immediately after operation starts. It then
the set current value). At the start of motor operation, a starting cur-
lowers and settles at the rated current. The peak current is about 5 to
rent several times the rated current flows and so to prevent the motor
6 times the rated current and takes from several seconds to several
circuit being tripped by the starting current, instantaneous operation
tens of seconds to settle to the rated current. This time varies largely
is not enabled until a fixed time tc has elapsed, as shown in the fig-
depending on type of motor and the nature of motor load (wt). There-
ure. Instantaneous operation starts after tc has elapsed. Motor start-
fore, it is necessary to obtain the motor’s starting time for operation
ing time “to” varies, depending on motor type, within a range from
with the load and to set a start-up lock time that allows for a margin of
several seconds to several tens of seconds. There are even slight dif-
error. Do not set an unnecessarily long start-up lock time. If the start-
ferences in starting time between the same type of motors and so be
up lock time is too long and an accident due to overcurrent occurs at
sure to set tc so that to totc, the motor circuit will
the start of operation, the trip signal will not be output until the start-
be tripped after tc has elapsed. The fixed time limit tc at the start of
up lock time has elapsed, possibly resulting in motor burnout.
motor operation is called “lock time”. The start-up detecting circuit
detects the starting operation level (30% max. of the set current
Overcurrent
time).
operating value
Start-up
operating value
Motor
Overcurrent operating value
A B C D E F G H
current
tc tc tc
* *
Motor current
to
to: Motor's starting time Operation
* ** **
mode
Start
tc: Lock time at start of operation
Start Start Start
tc
Output
Instantaneous operation enabled tc: Start-up lock time *: Fixed time-limit operation
Trip
Operating mode
**: Instantaneous operation enabled
Fixed time-limit
operation
6
Rectifier/smooth-
Reverse-phase Rectifier/smooth- Rectifier/smooth- Rectifier/smooth-
detecting circuit ing circuit
ing circuit ing circuit ing circuit
Open-phase Maximum value
To each circuit
detecting circuit
detecting circuit
Current-setting
circuit
Reverse-phase
Open-phase level Overcurrent
level detecting
Reset circuit
detecting circuit
circuit detecting circuit
Time-setting
circuit
OR circuit
Relay drive
circuit
Overcurrent
Start-up
detecting circuit
detecting circuit
Start time
setting circuit
Reverse-phase
detecting circuit
AND circuit Reset circuit Rectifier/smooth-
ing circuit
K2CM
2) Open-phase Circuit
Open-phase
switch Maximum phase of "High"
T phase
operating
current: R phase = 1.0
"Low" "High"
1.0 area
Open-phase Level Detecting Circuit
"Low"
Non-operating
This circuit detects when the current reaches the open-phase operat-
operating
area
area
ing level (85% max. of the set current value). Therefore, open-phase
A
is not detected until the maximum phase of the current exceeds 85%
of the set current value.
25%
Open-phase Detecting Circuit
35%
0.5
Output of the maximum value detecting circuit is divided and used as
reference values for comparison with the output of the rectifier/
smoothing circuits for the respective phases. If a phase has a value
60%
lower than the reference value, the K2CM judges it to be open-phase
and outputs an open-phase signal.
The following imbalance factors can be selected by setting the open-
phase switch.
0
0.5 1.0
“High” . . .Operating imbalance factor: 35 ±10%
S phase
“Low” . . .Operating imbalance factor: 60% min.
3) Reverse-phase Circuit
The imbalance factor can be easily obtained from the following
graph. In the graph, the horizontal axis indicates the maximum phase
of the current whereas the two vertical axes indicate the remaining
1. Current Reverse-phase Detection Models
two phases. The maximum phase of the current is taken to be 1.0 as
a reference point. The imbalance factor is obtained as a percentage
Reverse-phase Level Detecting Circuit
from the curve around the center of the graph. Obtain the imbalance
This circuit detects whether the current is in the operating level (50%
factor for a motor current with I = 100 A, I = 70 A, and I = 60 A as
R S T
max. of the set current value) as a precondition to detect the reverse-
follows:
phase.
1. On the R axis, locate point A, where I = 1.0.
R
Reverse-phase Detecting Circuit
2. Move from point A to point B, where I = 0.7 on the S axis.
S
3. On the T axis, locate point C, where I = 0.6.
The current reverse-phase detecting method is employed for detect-
T
ing reverse-phase as shown below. After the motor starts operating,
4. Follow the curves that pass through points B and C and locate the
the current phase becomes transiently unstable during T1 (approx.
intersection point D.
0.4 s) and so reverse-phase detection is not performed during this
5. Locating the point corresponding to point D on the imbalance fac-
period but it is performed during T2 (approx. 0.1 s). After T2 has
tor curve gives an imbalance factor of 36%. Take the maximum
elapsed, reverse-phase detection is not performed. For this reason,
phase of current on the horizontal axis without considering axes
this method cannot be applied to cases where instantaneous
R, S, and T.
reverse-phase is not permitted. When a reverse-phase is detected,
1.6 1.6 the relay is held in the latched state even after the motor current
stops (in both manual and automatic release types).
1.5 1.5
Start
1.4 1.4
1.3 1.3
Motor
T1
1.2 1.2
T2
1.1 1.1
Non-detecting area
1.0 1.0
Detecting area
0.9 0.9
T (R, S) 0.8 0.8 S (T, R)
2. Voltage Reverse-phase Detection Models
5.0
0.7 0.7 Point B
10.0
Reverse-phase Detecting Circuit
15.0
Point C 0.6 0.6
20.0 Reverse-phase detecting is performed by using the voltage reverse-
25.0
phase detection method.
0.5 0.5
30.0
35.0
0.4 0.4
Point D
40.0
45.0
0.3 0.3
50.0
55.0
U
60.0
0.2 0.2
65.0
V Reverse-phase output
70.0
75.0
0.1 0.1
80.0 W
85.0
90.0
95.0
0.0 0.0
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Point A
R (S, T)
Generally, in open-phase detection, detecting a complete open-
By voltage division within the above RC phase circuit, the output
phase is sufficient. In such a case, set the open-phase switch to the
becomes 0 V in the normal state or 1.5 V in the reverse-phase
“Low” position. If using the motor in an imbalanced condition causes
uv
problems, or when detecting internal open-phases of a delta-con- state. Using the output from this circuit, the reverse-phase level
nected motor, set the switch to the “High” position. Depending on the detecting circuit detects when the current reaches the reverse-phase
motor’s load condition and the imbalance of the power supply, how- operating level (80% or less of the control power supply).
ever, special consideration may be required for the detection of inter-
nal open-phases in delta-connected motors. Consult your OMRON
representative before using this method. When a transformer is con-
nected as a load, the harmonics increase at low loads. Therefore, in
such a case, set the open-phase switch to the “Low” position.
7
OR phase circuit
Reverse-phase level
detecting circuit
K2CM
Nomenclature
Trip Indicator
In normal operation, only the upper half of the display window is colored orange,
whereas when the motor circuit has tripped, the entire display window becomes orange.
Current-setting Knob
9
10 (side)By operating the setting knob, set the current value to
be equal to the rated current of the motor to be used.
The current-setting knob uses the same scale as the
rated current. Therefore, the operating value will be
115% of the set current value.
Example: Operating current value
= 12 × 1.15 (115%) = 13.8 A
The List of Current Settings shows an example. The
rated current differs depending on the motor’s type,
construction, manufacturer, etc. Therefore, set the
operating current after checking the specifications of
the motor.
Time-setting knob*
8 7 6
Test Button Reset Button
With manual resetting models, when the motor circuit trips during
Inverse Type
normal operation or test operation, the operation indicators and
Operation checks of the overcurrent function can be performed.
the output relay can be immediately reset by pressing the reset
Pressing the test button for the time-setting value will cause the motor
button.
circuit to trip.
When the motor circuit trips due to reverse-phase with automatic
With manual resetting models, even if the test button is released after
resetting models, the operation indicators and the output relay can
the motor circuit has tripped, the circuit remains tripped, whereas with
be immediately reset by pressing the reset button.
automatic resetting models, the motor circuit continues operating and
Reset button operation is ineffective when the operation power
the output relay releases.
supply is OFF. When the motor circuit trips during normal opera-
Be sure to perform the test operation with the overcurrent switch set to
tion, identify the abnormal input function by checking the LED indi-
ON. Set both the open-phase and reverse-phase switches to OFF. If
cators, then turn OFF the power switch of the main circuit and
one of these switches is set to ON, the motor circuit may trip if an
proceed with troubleshooting. After the abnormality is removed,
open-phase or reverse-phase occurs before an overcurrent does.
turn ON the power switch of the main circuit to reset the K2CM.
Instantaneous Type
Perform the test operation with input current at 0 and the overcurrent
Deciding the Number of Primary Conductor Passes
switch set to ON.
When using a motor with a small current rating, decide the num-
Pressing the test button for the set start-up lock time will cause the
ber of primary conductor passes through the current transformer
motor circuit to trip.
holes and the tap setting by referring to the List of Current Set-
With manual resetting models, even if the test button is released after
tings.
the motor circuit has tripped, the circuit remains tripped, whereas with
Pass all the three wires through the respective holes of the current
automatic resetting models, the motor circuit continues operating and
transformer. Basically, the wires should be passed through the
the output relay releases.
specified holes. If this is difficult, however, they can be passed
through any holes provided that the phase order is R, S, and T.
Time-setting Knob
1 pass 2 passes
Set the required operating time by operating the time-setting knob.
(With instantaneous-type models, the set operating time is used as the
start-up lock time).
Note: 1. The setting scale is the op-The scale multiplying factor
R R
S
S
erating time when 600% of can be selected by the time T
T
the current value is input. scale multiplying factor
If the wires are passed through the holes only once, a current within
switch.
2. The required operating
the full scale of the current-setting knob can be set. If they are
time varies depending on
passed more than once, however, the current setting range will
Scale Time scale
the type of motor, load con-
multiplying multiplying factor change according to the number of passes. The current setting
dition, etc. You can take the
factor switch
range when the number of conductor passes is n can be obtained
time from when the motor
Time scale × 1 (s) × 4 (s) by dividing the full scale of the current-setting knob by n. For exam-
starts to when the motor
value
ple, the current setting range of the K2CM-@@L@ is 8 to 26 A when
enters the steady state as
22 8 the wires are passed only once. This range is 4 to 13 A when the
a guide for setting this val-
wires are passed twice, 2 to 6.5 A when the wires are passed four
33 12
ue. When setting the oper-
times, and 1 to 3.25 A when the wires are passed eight times.
44 16
ating time for submersible
The wires can be passed through the holes any number of times. It
motors, which require very 55 20
is convenient for the calculation, however, if the number of passes
short operating times, con-
66 24
is 2, 4, or 8.
sult the manufacturer to
77 28The signal from a high-voltage motor is input to the Motor Protec-
obtain the correct operat-
tive Relay via an external current transformer. In this case, the cur-
88 32
ing time. An operating time
rent can be set in the same manner as above by dividing the rated
99 36
shorter than 5 s can be
current of the high-voltage motor by the transformation ratio of the
used as a rough guide.
10 10 40
current transformer.
8
K2CM
3. Reverse-phase Setting Switches
LED Indicators
These switches select the reverse-phase detection function and
When the motor circuit trips due to overcurrent, open-phase, or
reverse-phase polarity. By selecting the reverse-phase polarity
reverse-phase, the respective LED indicator lights (continuously).
accordingly, the K2CM can operate normally without changing the
The overcurrent indicator also indicates the start of operation.
connections when wired with the order of the phases reversed.
Overcurrent operating value
Reverse-phase ON Enabled
(115% of current-setting value)
detecting
OFF Disabled
Motor current
function
Bright Bright
Reverse-phase Normal The motor circuit trips at reverse-
Dimmed
polarity phase when a reverse-phase is
detected.
Reverse Used when a reverse-phase
Start Trip
connection is made in the power line
• With the inverse-type models, when the motor current exceeds the
of the motor at a point before the
overcurrent operating value, the overcurrent indicator blinks at the
current transformer (including
bright level and then remains lit at the dimmed level. After the oper-
external current transformer).
ating time has elapsed, with the manual resetting models, the
motor circuit trips and the overcurrent indicator remains lit at the
If the K2CM detects reverse-phase although the motor is rotating in
bright level, whereas with automatic resetting models, the indicator
the forward direction (e.g., because of incorrect wiring of power
remains lit at the bright level until the motor current descends below
lines), set the reverse-phase polarity switch to the “Reverse” position
the resetting value.
to enable normal operation.
• Since the indicator status is not stored in memory when the opera-
Phase condition Normal Reverse Reverse
tion power supply is turned OFF, be sure to check which indicators
were illuminated when the motor circuit was tripped.
RS T RS T RS T
Connections
(A) (C)
The functions of the K2CM can be used in the following seven com-
RS T RS T RS T
binations. For each function, turn ON the corresponding setting
Motor Motor
Motor
switch.
relay relay relay
(D)
(B)
Function Overcurrent Open-phase Reverse-phase M M M
Combination
Reverse-phase Normal Normal Normal
1ON
polarity switch
position
2ON
Trip None Yes None
3ON
Direction of Forward Reverse Reverse
4ON ON
motor rotation (See below.)
5ONON
6ON ON
7ON ON ON
Reverse Reverse Reverse Reverse
Coun- Reverse-
When the setting switches for overcurrent, open-phase, or reverse-
ter- phase
phase function are turned OFF, the following functions becomes
mea- polarity
invalid.
sure switch
position
Function setting switch Invalid function
Wiring Wiring Wiring Wiring
Wiring
set to OFF
changed changed changed changed
at (A). at (B). at (C). at (D).
Overcurrent Time setting and multiplication
Open-phase “High” and “Low” imbalance factors
Reverse-phase “Forward” and “Reverse” function
Direction of Forward
1. Overcurrent Setting Switches
motor rotation
These switches select the overcurrent setting and the multiplying
factor linked with operating time setting. Note: The K2CM detects reverse-phase at a point before the current
transformer. If a reverse connection is made at the load side far
Overcurrent ON Enabled
from the current transformer and the motor rotates in the re-
detecting function
verse direction, the K2CM does not detect the reverse-phase.
OFF Disabled
Time setting × 4 (s) Time setting scale value × 4 = 8 to 40 s
Reverse-detectable Range
multiplying factor
× 1 (s) Time setting scale value × 1 = 2 to 10 s
RS T
Detectable: Reverse-phase state can be detected with the
2. Open-phase Setting Switches
motor protective relay only on the power supply
RS T
side.
These switches select the open-phase detecting function and the
“High” or “Low” current imbalance factor for operation.
Undetectable: Reverse-phase state on the motor side cannot
M
be detected with the motor protective relay.
Open-phase ON Enabled
* The OR phase circuit in the above figure combines a resistor and
detecting
OFF Disabled
capacitor. The reverse phase detection circuit detects when the
function
reversed signals detected by the OR phase circuit reach the oper-
Imbalance factor High The motor circuit operates at an
ating level (i.e., 80% or less of the control power supply voltage).
operating imbalance factor of 35
±10%.
Low The motor circuit operates at an
operating imbalance factor of 60%.
9
K2CM
Engineering Data
Overload Operating Time Overload Operating Time
Characteristics for Inverse Type Characteristics for Instantaneous Type
Time scale multiplying factor
(× 4) (× 1)
280 70
0.2
This graph shows the
behavior when the
240 60
current changes from
100% of the current-
setting value to the
200 50 Time scale
percentage shown on
10
the horizontal axis.
8
160 40
6
0.1
120 30
4
2
80 20
40 10
0
0 0
100 200 300 400 500 600 700
100 200 300 400 500 600 700
Motor current (percentage of current-setting value)
Motor current (percentage of current-setting value)
Typical Characteristics of Typical Characteristics of
Open-phase Operation Reverse-phase Operation
2.0
0.6
This graph shows the behavior when
This graph shows the behavior when
the current changes from 100% of the
the current changes from 100% of the
current-setting value to the percentage
current-setting value to the percentage
0.5
shown on the horizontal axis.
shown on the horizontal axis.
0.4
1.0
0.3
0.2
0.1
0
100 200 300 400 500 600 700 0
100 200 300 400 500 600 700
Motor current (percentage of current-setting value)
Motor current (percentage of current-setting value)
10
Operating time (s)
Operating time (s)
Operating time (s)
Operating time (s)
K2CM
Dimensions
Note: All units are in millimeters unless otherwise indicated.
Surface-mounting Models
126
80
6
60 52 46.5
11.5
48.5
15
4
55
33
11
Six, M3 terminal screws
Four, 6-dia. mounting holes or
four, M5 mounting-screw holes
120
52±0.5
36
80±0.5
33.5
33.5
Three, 20-dia. holes
Operating Procedures
■ Operation, Setting, and Indication
Based on the current value of the motor to be used, perform the setting of each item of the K2CM Motor Protective Relay.
List of Current Settings (when using a 200-VAC motor)
Type* K2CM-@@LS@ K2CM-@@L@ K2CM-@@M@ K2CM-@@H@
Number of passes 1124 8 1 1
Setting Time scale value 2 to 8 8 to 26 20 to 65 50 to 160
Current setting range (A) 2 to 8 8 to 26 4 to 13 2 to 6.5 1 to 3.25 20 to 65 50 to 160
Motor*** Rated output (kW) Rated current (A)**
0.2 1.8
0.4 2.8
0.75 4.2
1.5 7.3
2.2 10
3.7 16.1
5.5 24
7.5 32
11 45
15 61
18.5 74
22 87
30 117
37 143.0
* The squares (@) represent the symbols defined under Model Number Legend.
** The rated current is the current at full load.
*** Supply: Low-voltage 3-phase basket type inductive motor, full-load characteristics of 200 VAC, 4-pole, totally-enclosed.
Note: When using a large-capacity or high-voltage motor whose capacity is 45 kW or more, calculate the rated current/alternating current ratio by
converting with the alternating current ratio of the external current transformer.
11
K2CM
Testing Method
200 V
50/60 Hz
■ Current Reverse-phase Detection Models (3-phase)
U VW
The operating characteristics listed in the table below are tested using the circuit shown on the right. Decide the number of conductor
100 VAC
passes through the holes of the current transformer in accordance with the operating current range of the Motor Protective Relay and by
50/60Hz
SW1
referring to the current setting method described under Operation, Setting, and Indication.
3φSD
Y
CC
100 V
C
±
SW2
a1 c1 b2 c2 s1 s2
Minimum set time is 2 s.
K2CM Motor Protective Relay
3φSD: Three-phase voltage regulator (5 to 15 A) R1: Variable resistor (50 Ω, 400 W + 400 W)
R1 R1
A: AC ammeter (5 A) R2: Fixed resistor (50 Ω, 400 W + 400 W)
V: AC voltmeter (300 V) SW1: Knife switch (3-phase)
CC: Cycle counter SW2: Toggle switch
Y: Auxiliary relay (15 A)
R2
Test item Test procedure
Operating value Operating time
Over- Inverse type 1. Turn ON SW1. 1. Turn ON SW1 and SW2. Increase the current to 600% of
current the set current value by adjusting the voltage regulator.
2. Turn ON SW2 to operate auxiliary relay Y.
Turn OFF SW1 and SW2.**
3. Gradually increase the current by adjusting the voltage
2. Turn ON SW1.
regulator. With inverse-type models, read the value of the
current when the overcurrent LED indicator blinks. With 3. Turn ON SW2 and read the position (i.e., time) of the
instantaneous-type models, read the value when it lights pointer of cycle counter CC when CC is stopped by the
(continuously).* operation of the K2CM. The read time is the operating time
for inverse-type models and the lock time of the instanta-
4. Turn OFF SW1 and SW2.
neous-type models.
4. Turn OFF SW1 and SW2.
Instantaneous 1. Turn ON SW1 and SW2. Increase the current to 100% of
type the set current value by adjusting the voltage regulator.
Turn OFF SW1 and SW2.
2. Turn ON SW1 and SW2 again and wait 2 seconds mini-
mum.
3. Using the voltage regulator, abruptly increase the current
to 140% of the set current value. Confirm that the K2CM
performs instantaneous operation.
4. Turn OFF SW1 and SW2.
Open-phase 1. Open (disconnect) any one of the input phases for the cur- 1. Open (disconnect) any one of the input phases for the cur-
rent transformer. rent transformer.
2. Turn ON SW1 and SW2. Gradually increase the current by 2. Turn ON SW1 and SW2. Increase the currents of the other
adjusting the voltage regulator. two phases to 115% of the set current value by adjusting
the voltage regulator. Turn OFF SW1 and SW2 temporarily.
3. Confirm that the K2CM operates at a current no greater
than 85% of the set current value and that, at this current, 3. Turn ON SW1 and SW2 again. Read the position (i.e.,
the trip indicator is orange and the open-phase LED indica- time) of the pointer of cycle counter CC when CC is
tor lights. stopped by the operation of the K2CM.
4. Turn OFF SW1 and SW2. 4. Turn OFF SW1 and SW2.
Reverse-phase 1. Interchange any two phases at a position closer to the 1. Interchange any two phases at a position closer to the
power supply than the current transformer. (In the above power supply than the current transformer. (In the above
figure, phases U and V are interchanged as shown by the figure, phases U and V are exchanged as shown by the
dotted lines.) dotted lines.)
2. Turn ON SW1 and SW2. Decrease the current to 50% of 2. Turn ON SW1 and SW2. Increase the current to 100% of
the set current value by adjusting the voltage regulator. the set current value by adjusting the voltage regulator.
Then turn OFF SW1 and SW2 temporarily. Then turn OFF SW1 and SW2 temporarily.
3. Turn ON SW1 and SW2 again. Confirm that the K2CM 3. Turn ON SW1 and SW2 again. Read the position (i.e.,
operates, the trip indicator is orange, and that the reverse- time) of the pointer of cycle counter CC when CC is
phase LED lights. stopped by the operation of the K2CM.
4. Turn OFF SW1 and SW2. 4. Turn OFF SW1 and SW2.
* Balance the currents between phases by adjusting variable resistor R1.
** If a current equal to 600% of the set current value cannot be attained by adjusting the voltage regulator, increase the number of conductor passes
through the holes of the current transformer.
12
K2CM
■ Voltage Reverse-phase Detection Models
The operating characteristics listed in the table below are tested
using the circuit shown on the right. Decide the number of conductor
200 V
50/60 Hz
passes through the holes of the current transformer in accordance
(3-phase)
with the operating current range of the Motor Protective Relay and by U VW
referring to the current setting method described under Operation,
Setting, and Indication.
SW1
100 VAC
50/60 Hz
3φSD
Y
CC
100 V
C
±
SW2
Ta Tc Tb U VW
Minimum set time is 2 s.
K2CM Motor Protective Relay
3φSD: Three-phase voltage regulator (5 to 15 A) R1: Variable resistor (50 Ω, 400 W + 400 W)
R1 R1
A: AC ammeter (5 A) R2: Fixed resistor (50 Ω, 400 W + 400 W)
V: AC voltmeter (300 V) SW1: Knife switch (3-phase)
CC: Cycle counter SW2: Toggle switch
Y: Auxiliary relay (15 A)
R2
Test item Test procedure
Operating value Operating time
Over- Inverse type 1. Turn ON SW1. 1. Turn ON SW1 and SW2. Increase the current by adjusting
current the voltage regulator to 600% of the set current value.
2. Turn ON SW2 to operate auxiliary relay Y.
Turn OFF SW1 and SW2.**
3. Gradually increase the current by adjusting the voltage
2. Turn ON SW1.
regulator. With inverse-type models, read the value of the
current when the overcurrent LED indicator blinks. With 3. Turn ON SW2 and read the position (i.e., time) of the
instantaneous-type models, read the value when it lights pointer of cycle counter CC when CC is stopped by the
(continuously).* operation of the K2CM. The read time is the operating time
for inverse-type models and the lock time of the instanta-
4. Turn OFF SW1 and SW2.
neous-type models.
4. Turn OFF the SW1 and SW2.
Instantaneous 1. Turn ON SW1 and SW2. Increase the current to 100% of
type the set current value by adjusting the voltage regulator.
Then turn OFF SW1 and SW2.
2. Turn ON SW1 and SW2 again and wait 2 seconds mini-
mum.
3. Using the voltage regulator, abruptly increase the current
to 140% of the set current value. Confirm that the K2CM
performs the instantaneous operation.
4. Turn OFF SW1 and SW2.
Open-phase 1. Open (disconnect) any one of the input phases for the cur- 1. Open (disconnect) any one of the input phases for the cur-
rent transformer. rent transformer.
2. Turn ON SW1 and SW2. Gradually increase the current by 2. Turn ON SW1 and SW2. Increase the currents of the other
adjusting the voltage regulator. two phases to 115% of the set current value by adjusting
the voltage regulator. Turn OFF SW1 and SW2 temporarily.
3. Confirm that the K2CM operates at a current no greater
than 85% of the set current value and that, at this current, 3. Turn ON SW1 and SW2 again. Read the position (i.e.,
the trip indicator is orange and the open-phase LED indica- time) of the pointer of cycle counter CC when CC is
tor lights. stopped by the operation of the K2CM.
4. Turn OFF SW1 and SW2. 4. Turn OFF SW1 and SW2.
Reverse-phase 1. Change the phase sequence to reverse-phase by switch- 1. Put the voltage input in the reverse-phase state.
ing the U and W input terminals of the K2CM as shown by
2. Turn ON SW1 and SW2 and read the position of the
the dotted lines.
pointer of cycle counter CC when CC is stopped.
2. Turn ON SW1 and SW2 and confirm that the K2CM oper-
3. Turn OFF SW2.
ates.
3. Add a three-phase voltage regulator to the U, V, and W ter-
minal inputs.
4. Adjust the voltage regulator and confirm that the K2CM
operates at less than 80% of the rated supply voltage.
* Balance the currents between phases by adjusting variable resistor R1.
** If a current equal to 600% of the set current value cannot be attained by adjusting the voltage regulator, increase the number of conductor passes
through the holes of the current transformer.
13
K2CM
Safety Precautions
A power supply with a frequency other than commercial frequency
■ Correct Use
cannot be used as the control power supply.
The operation check using the test button is intended to check theUse of circuits containing a high percentage of harmonics, such as
operation of the overcurrent functions. Therefore, be sure to turn circuits incorporating SCR control circuits, VVVF inverters, or recti-
ON the overcurrent switch. Also, at this time, turn OFF the open- fiers, may cause errors and malfunctions. Consult your OMRON
phase switch and reverse-phase switch to prevent unnecessary representative for details.
operations from being performed.When applying the K2CM to the protection of a high-voltage motor
The operating time of inverse-type models and the lock time of the or low-voltage, high-capacity motor, use an external rectifier that
instantaneous-type models depend upon the set operating time. does not saturate at currents up to 600% of the rated motor current
Therefore, do not hold down the test button for more than the set and thus permits a large overcurrent; otherwise, the K2CM will out-
operating time. put a tripping signal because of imbalanced operation when an
overcurrent occurs and, with reverse-type models, the motor mayThe reverse-phase can be detected in the wiring up to the current
be damaged by burning.
transformer (including an external current transformer). Check the
wiring between the current transformer and the motor before start-Never tamper with the trip indicator. Use the reset switch to reset
ing the motor. the K2CM.
Current reverse-phase detection models cannot be used in applica-When a power failure occurs in the control power supply, the K2CM
tions that do not allow even momentary reversals of motor direc- is not reset even when the reset switch is pressed. This is not an
tion. error. The K2CM can be reset only when control power is applied to
it.Jogging of the motor can be performed. For details, consult your
OMRON representative.Be sure to remount the front cover after detaching it for operating or
setting the switches on the front panel.When using the K2CM to control inching shorter than 0.5 s, the
reverse-phase level detection circuit may operate. In this case, beThe rectifier and control circuits are combined by tightening the two
sure to use the K2CM with the reverse-phase switch set to OFF. screws on the right and left sides. Never loosen these screws.
The K2CM is basically intended to protect three-phase loads. ItsThe variable resistors used to make settings are equipped with
overcurrent function, however, can also be applied to single-phase mechanisms to stop them rotating outside the valid scale range. Do
loads. In this case, the conductors can be passed through the holes not rotate the variable resistors at a torque of 1 kg·cm or more.
in any direction and sequence.When using the K2CM-@@@A (instantaneous, automatic reset-
When applying the K2CM to a circuit with a high imbalance factor ting), be sure to apply power to the Motor Protective Relay from the
due to the nature of the power supply or load, actually measure the same power line as the magnet contactor for switching the motor.
imbalance factor and select the open-phase sensitivity accordinglyBe sure to provide the control power supply for the K2CM-@@@@V
(i.e., set the open-phase switch to either the high or low position).
(voltage reverse-phase detection) from the same line as the motor.
The K2CM cannot be used if the imbalance factor is 60% or higher.
If current reverse-phase detection models are used in a circuit with
When applying the K2CM to the protection of three-phase trans-
distorted current waveforms, the reverse-phase element may per-
formers, give consideration to the imbalance factor due to single-
form an unwanted operation. In such circuits, use of the K2CM-
phase loads.
@@@@V (voltage reverse-phase detection) is recommended
because it is not affected at all by current waveform distortion.
Combination Function setting switches LED indicators NOTE
Overcur- Open- Reverse- Overcur- Open- Reverse-
rent phase phase rent phase phase
1 ON ON If the inputs for combinations of two or more functions are
simultaneously generated, the K2CM detects the inputs in
2ON ON
the order reverse-phase, open-phase, overcurrent. Take
3ONOFFON
combination 4 as an example. If the open-phase and over-
4ON ON ON current occur at the same time, there is insufficient time to
detect the overcurrent because the open-phase is first de-
5ONON OFFON
tected and the K2CM outputs the tripping signal (causing
6ON ON OFF ON
the magnet contactor to turn off). Therefore, the overcur-
7 ONON ONOFF OFF ON rent indicator does not light.
14
K2CM
■ Maintenance and Inspection
Q&A
The K2CM Motor Protective Relay offers very stable characteristics.
To maintain these characteristics for a long time, the following
inspections are recommended.
What is the VA consumption of the CT section?
Q
Daily Inspection
The consumption is 0.4 VA/phase max. for any CT section.
The purpose of daily inspection is to discover causes of failure before
using the Motor Protective Relay. This inspection depends somewhat
on the perception of the operator as it includes visual checking, etc.
Classification Inspection items
What action is required if an inverter circuit is used?
Q
Connections Loosening, damage, and dust collection at
screw terminals, damage to wiring insulation
sheaths, excessive force applied on wirings,
As shown in the following figure, insert the K2CM and turn
adhesion of foreign objects to terminal
OFF the reverse-phase switch before using the K2CM.
screws
Motor Protective Relay Adhesion of foreign objects and dust to the
operation panel, shift of set value, indication
Inverter K2CM
status of operation indicators and trip indica- M
tor, presence/absence of front cover, loos-
Motor
ening of screws combining rectifier and
control circuits, deformation of case, abnor-
Always insert the K2CM on the secondary side (load side)
mal temperature on housing surface
of the inverter.
External rectifier Loosing of terminals, unusual odor, discolor-
Mounting Inverter power Inverter load
ation of surface
location supply
Element
Periodic Inspection
Overcurrent NG Conditionally OK
Open-phase NG Conditionally OK
This inspection is performed by turning OFF the power at regular
intervals to check the aging caused by long-time operation. It is rec-
Reverse-phase NG NG
ommended that periodic inspection is performed once a year.
Error may occur in the operating values depending on the
inverter specifications and settings. Set the values after
Motor Protective Relay
performing tests and confirming operation.
Classification Inspection item
The current waveform on the inverter power supply side is
Construction Adhesion of dust and foreign objects to
distorted, so the K2CM may malfunction.
terminals, cracks in insulators around
The inverter load side contains a large high-frequency
terminal block, burn damage to wirings,
component, so the K2CM may malfunction due to phase
damage to setting knobs, selector
reversal.
switches, test button, and reset button,
damage to insulators of solderless ter-Depending on the specifications and settings of the
minals, rust and discoloration of screw inverter, overloads and open phases may also cause the
terminals K2CM to malfunction.
Operating characteristics Refer to Testing Method.
Insulation resistance Between terminals and mounting panel
Operation check with test Checking of operating time, operation What action is required if single phase is used?
Q
button indicators, and trip indicator
The following describes the operating procedure for using a
External Rectifier single phase with the K2CM.
Connection Method
Check for adhesion of dust and foreign objects, damage to wirings by
Pass wires through any two of the three holes on the
burning, and loosening of mounting screws.
K2CM.
K2CM
M
Motor
If a single phase is used, set the open-phase and reverse-
phase switch to OFF. Make the overload settings so that
they match the motor current.
Do not apply control power supply voltage between the V-
W terminals if a model with voltage reverse-phase
detection is used.
ALL DIMENSIONS SHOWN ARE IN MILLIMETERS.
To convert millimeters into inches, multiply by 0.03937. To convert grams into ounces, multiply by 0.03527.
In the interest of product improvement, specifications are subject to change without notice.
15
Terms and Conditions Agreement
Read and understand this catalog.
Please read and understand this catalog before purchasing the products. Please consult your OMRON representative if you
have any questions or comments.
Warranties.
(a) Exclusive Warranty. Omron’s exclusive warranty is that the Products will be free from defects in materials and workmanship
for a period of twelve months from the date of sale by Omron (or such other period expressed in writing by Omron). Omron
disclaims all other warranties, express or implied.
(b) Limitations. OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, ABOUT
NON-INFRINGEMENT, MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE OF THE PRODUCTS. BUYER
ACKNOWLEDGES THAT IT ALONE HAS DETERMINED THAT THE
PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIR INTENDED USE.
Omron further disclaims all warranties and responsibility of any type for claims or expenses based on infringement by the
Products or otherwise of any intellectual property right. (c) Buyer Remedy. Omron’s sole obligation hereunder shall be, at
Omron’s election, to (i) replace (in the form originally shipped with Buyer responsible for labor charges for removal or
replacement thereof) the non-complying Product, (ii) repair the non-complying Product, or (iii) repay or credit Buyer an amount
equal to the purchase price of the non-complying Product; provided that in no event shall Omron be responsible for warranty,
repair, indemnity or any other claims or expenses regarding the Products unless Omron’s analysis confirms that the Products
were properly handled, stored, installed and maintained and not subject to contamination, abuse, misuse or inappropriate
modification. Return of any Products by Buyer must be approved in writing by Omron before shipment. Omron Companies shall
not be liable for the suitability or unsuitability or the results from the use of Products in combination with any electrical or
electronic components, circuits, system assemblies or any other materials or substances or environments. Any advice,
recommendations or information given orally or in writing, are not to be construed as an amendment or addition to the above
warranty.
See http://www.omron.com/global/ or contact your Omron representative for published information.
Limitation on Liability; Etc.
OMRON COMPANIES SHALL NOT BE LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL, OR CONSEQUENTIAL DAMAGES,
LOSS OF PROFITS OR PRODUCTION OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,
WHETHER SUCH CLAIM IS BASED IN CONTRACT, WARRANTY, NEGLIGENCE OR STRICT LIABILITY.
Further, in no event shall liability of Omron Companies exceed the individual price of the Product on which liability is asserted.
Suitability of Use.
Omron Companies shall not be responsible for conformity with any standards, codes or regulations which apply to the
combination of the Product in the Buyer’s application or use of the Product. At Buyer’s request, Omron will provide applicable
third party certification documents identifying ratings and limitations of use which apply to the Product. This information by itself
is not sufficient for a complete determination of the suitability of the Product in combination with the end product, machine,
system, or other application or use. Buyer shall be solely responsible for determining appropriateness of the particular Product
with respect to Buyer’s application, product or system. Buyer shall take application responsibility in all cases.
NEVER USE THE PRODUCT FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE OR PROPERTY OR IN LARGE
QUANTITIES WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TO ADDRESS THE RISKS,
AND THAT THE OMRON PRODUCT(S) IS PROPERLY RATED AND INSTALLED FOR THE INTENDED USE WITHIN THE
OVERALL EQUIPMENT OR SYSTEM.
Programmable Products.
Omron Companies shall not be responsible for the user’s programming of a programmable Product, or any consequence
thereof.
Performance Data.
Data presented in Omron Company websites, catalogs and other materials is provided as a guide for the user in determining
suitability and does not constitute a warranty. It may represent the result of Omron’s test conditions, and the user must correlate
it to actual application requirements. Actual performance is subject to the Omron’s Warranty and Limitations of Liability.
Change in Specifications.
Product specifications and accessories may be changed at any time based on improvements and other reasons. It is our
practice to change part numbers when published ratings or features are changed, or when significant construction changes are
made. However, some specifications of the Product may be changed without any notice. When in doubt, special part numbers
may be assigned to fix or establish key specifications for your application. Please consult with your Omron’s representative at
any time to confirm actual specifications of purchased Product.
Errors and Omissions.
Information presented by Omron Companies has been checked and is believed to be accurate; however, no responsibility is
assumed for clerical, typographical or proofreading errors or omissions.
2016.4
In the interest of product improvement, specifications are subject to change without notice.
OMRON Corporation
Industrial Automation Company
http://www.ia.omron.com/
(c)Copyright OMRON Corporation 2016 All Right Reserved.
What they say about us
FANTASTIC RESOURCE
One of our top priorities is maintaining our business with precision, and we are constantly looking for affiliates that can help us achieve our goal. With the aid of GID Industrial, our obsolete product management has never been more efficient. They have been a great resource to our company, and have quickly become a go-to supplier on our list!
Bucher Emhart Glass
EXCELLENT SERVICE
With our strict fundamentals and high expectations, we were surprised when we came across GID Industrial and their competitive pricing. When we approached them with our issue, they were incredibly confident in being able to provide us with a seamless solution at the best price for us. GID Industrial quickly understood our needs and provided us with excellent service, as well as fully tested product to ensure what we received would be the right fit for our company.
Fuji
HARD TO FIND A BETTER PROVIDER
Our company provides services to aid in the manufacture of technological products, such as semiconductors and flat panel displays, and often searching for distributors of obsolete product we require can waste time and money. Finding GID Industrial proved to be a great asset to our company, with cost effective solutions and superior knowledge on all of their materials, it’d be hard to find a better provider of obsolete or hard to find products.
Applied Materials
CONSISTENTLY DELIVERS QUALITY SOLUTIONS
Over the years, the equipment used in our company becomes discontinued, but they’re still of great use to us and our customers. Once these products are no longer available through the manufacturer, finding a reliable, quick supplier is a necessity, and luckily for us, GID Industrial has provided the most trustworthy, quality solutions to our obsolete component needs.
Nidec Vamco
TERRIFIC RESOURCE
This company has been a terrific help to us (I work for Trican Well Service) in sourcing the Micron Ram Memory we needed for our Siemens computers. Great service! And great pricing! I know when the product is shipping and when it will arrive, all the way through the ordering process.
Trican Well Service
GO TO SOURCE
When I can't find an obsolete part, I first call GID and they'll come up with my parts every time. Great customer service and follow up as well. Scott emails me from time to time to touch base and see if we're having trouble finding something.....which is often with our 25 yr old equipment.
ConAgra Foods